Author Message
neofrig
Refrigerator

Posts: 3
Since: 07/Oct/2010

 pressure and discharge temperature
- Publicidad -

Good afternoon, the truth is that my papers were burned so I turn to someone who can and has the vondad to help me, the problem is the following: I have a cold center that works with R22, in which I have a discharge pressure of 250 PSI and about 49 ºC at the entrance of the capacitor and about 30 º C at the exit, because of the symptoms I think what it has is air in the system, I am purging through a siphon but I do not get improvements. the question is I'm misdiagnosing? It is worth clarifying that I do not have liquid in the hall ... and the plant does not perform..


07/Oct/2010 21:39 GMT+1 presion ytemperatura de descargaProfile· 0Private
neofrig
Refrigerator

Posts: 3
Since: 07/Oct/2010

1 RE: pressure and discharge temperature

Originally written by neofrig

Good afternoon, the truth is that my papers were burned so I turn to someone who can and has the vondad to help me, the problem is the following: I have a cold center that works with R22, in which I have a discharge pressure of 250 PSI and about 49 ºC at the entrance of the capacitor and about 30 º C at the exit, because of the symptoms I think what it has is air in the system, I am purging through a siphon but I do not get improvements. the question is I'm misdiagnosing? It is worth clarifying that I do not have liquid in the hall ... and the plant does not perform..


207/Oct/2010 21:39 GMT+1 3Profile· 4Private
glacial-R
Frigorista & Forum Administrator

Posts: 983
Since: 03/Jan/2005

5 RE: pressure and discharge temperature

If your doubt is that there is air in the circuit, the best option is to unload everything, vacuum and recharge.


608/Oct/2010 03:01 GMT+1 7Profile· 8Private
neofrig
Refrigerator
- Publicidad -

Posts: 3
Since: 07/Oct/2010

9 RE: pressure and discharge temperature

from now on thank you very much and if what I did was exactly that, only they did not give me too much time to empty since it is a bakery plant and the machine stop means stopping the production, then vent as much as I could and reload, since it is a cold plant of 200 Hp simple stage but anyway thank you.


008/Oct/2010 22:36 GMT+1 1Profile· 2Private
Cold
Premiun Refrigerator

Posts: 126
Since: 18/May/2004

3 RE: pressure and discharge temperature

Originally written by neofrig

from now on thank you very much and if what I did was exactly that, only they did not give me too much time to empty since it is a bakery plant and the machine stop means stopping the production, then vent as much as I could and reload, since it is a cold plant of 200 Hp simple stage but anyway thank you.


Uff!! ... I think you made the mistake of accepting to be controlled for the time needed to make a good empty, because a 200hp equipment has to be a lot of coolant to eliminate due to a bad maneuver ... Although I admit that it is difficult to make the client understand the time and materials that must be invested to do a good job, ... there is no lack of the master who competes with you for less time and fewer materials, and the customer who buys with him.

I hope it does not cause you many problems because you will have to wait for the next failure.


408/Oct/2010 23:05 GMT+1 5Profile· 6Private
Advertising

Authors: Solutions in Refrigeration and Air Conditioning

See original.

RefriAméricas 2025: the academic program is available and the registration discount is in force

RefriAméricas 2025: the academic program is available and the registration discount is in force

Dominican Republic. A little more than a month after its implementation, RefriAméricas 2025 continues to advance in its agenda. The event, which will be held on July 23 and 24 in Santo Domingo,...

New Board of Directors to Lead ADOMTRA for 2025-2027

New Board of Directors to Lead ADOMTRA for 2025-2027

Dominican Republic. The Dominican Association of Refrigeration and Air Conditioning Technicians announced the formation of its new Board of Directors for the period 2025-2027, elected during the...

Bogota to host key building automation event in Latin America

Bogota to host key building automation event in Latin America

Colombia. On July 11, the Tequendama Suites Hotel will be the meeting point for leaders in the technology sector with the Building Automation Days by KNX LATAM Colombia, an event that will bring...

Ductless heat pumps prove effective in cold climates

Ductless heat pumps prove effective in cold climates

International. Ductless heat pumps are defying low temperatures with increasingly advanced technologies, establishing themselves as a reliable solution for heating in regions with harsh winters.

Frascold launches new ATEX-HT compressor series for high temperatures and low emissions

Frascold launches new ATEX-HT compressor series for high temperatures and low emissions

Italy. The new line is designed to operate with natural hydrocarbons and reach temperatures of up to 135°C, expanding sustainable options for heating and industrial processes.

Intelligent Cooling Drives Efficiency and Sustainability in Data Centers

Intelligent Cooling Drives Efficiency and Sustainability in Data Centers

International. As technology infrastructure expands to sustain the growing demand for data, so does its environmental impact. Data centers, essential to global digital operations, face the challenge...

High-precision logistics: the cold chain that saves lives in the Mexican health system

High-precision logistics: the cold chain that saves lives in the Mexican health system

Mexico. High-precision medical logistics has established itself as a strategic component in the health sector, where a minimum thermal deviation can represent millions of dollars in losses or, even...

Technical Training: Honeywell Hosts Workshop on New Generation of Solstice Refrigerants

Technical Training: Honeywell Hosts Workshop on New Generation of Solstice Refrigerants

International. This Thursday, June 12, 2025, Honeywell will hold the first session – in virtual format – of the training workshop "Solstice Refrigerants: The New Generation of Refrigerants with Low...

Cleveland Controls Launches Universal Adjustable Air Pressure Switch for Multiple Applications

Cleveland Controls Launches Universal Adjustable Air Pressure Switch for Multiple Applications

United States. Cleveland Controls announced the launch of its new ANS2 series of air pressure switches, a universal, field-adjustable device developed for a wide range of applications in residential...

Trane Renews Leadership in Mexico and Latin America with Three Strategic Appointments

Trane Renews Leadership in Mexico and Latin America with Three Strategic Appointments

Mexico. Trane announced a key restructuring of its management team for Mexico and Latin America. The changes are part of a strategy to consolidate its presence in key markets and strengthen its...

Free Subscription
Remember Me
SUBSCRIBE TO OUR NEWSLETTER
DO YOU NEED A SERVICE OR PRODUCT QUOTE?
LASTEST INTERVIEWS
SITE SPONSORS










LASTEST NEWSLETTER
Ultimo Info-Boletin