Select your language

Load losses in refrigeration pipes

One of the main challenges of every refrigeration system designer is, without a doubt, the selection of the pipe for a correct performance of the system.

by Alonso Amor*

To perform this task one of the parameters that must be considered is the loss of load generated along the entire refrigeration circuit. Pressure loss (or pressure drop) is the pressure differential measured at two different points in the system.

There are points where a pressure drop is necessary as is the case of the expansion valve, however, a pressure differential in other components is not desirable because these losses will cause an inefficient performance of the system generating a greater energy consumption for the end user. 

- Publicidad -

Pressure drops are totally inevitable, since every fluid moving within a delimited volume will have a pressure differential caused by the resistance of the medium represented by friction, being that, the longer the length of the pipe, the greater this differential. The rule is simple, a higher speed implies a greater loss and a smaller diameter greater speed. 

If we strictly apply the previous statement, the pipe with a larger diameter will always be the best, since this way we will have lower speeds and lower losses, causing a greater efficiency. But when we begin to think from a practical point of view, the larger the diameter, the greater the demand for refrigerant fluid and with this we reach new problems since an excessive load is always a complication for the control of liquid, in addition, from the perspective of the end user, the use of larger diameters will always be a greater investment and this can make the installation unfeasible.

It should be borne in mind that inside a pipe it is not only refrigerant that is circulating, there is also a portion of oil that in combination with the refrigerant must return safely to the compressor. To achieve this we must guarantee sufficiently high speeds that promote a correct drag of the oil, being that, high speeds will bring as a consequence greater pressure drops.

Due to the complexity of the problem, there is no exact equation or method that results in the pipe diameter that must be used in each of the segments of the circuit, which is why the designer must know the principles of selection and apply them correctly always looking for an adequate functioning of the system.

Suction line

The suction line is the segment of the cycle where the correct selection of the pipe is most critical since any pressure drop in this stretch will generate a higher compression ratio directly affecting the efficiency of the system. The selection of this line should be based on the pressure drop equivalent to 1.1 °K taking as a reference the evaporation temperature of the system (see table 1).

The pipe must follow the most direct path possible avoiding the installation of unnecessary curves that can generate an additional loss of pressure. In the same way, all those components that are not totally necessary for the operation of the application, such as pressure regulating valves or unspecified filters, should be avoided. 

- Publicidad -

Table 1: Pressure drop equivalent to 1.1 K at different evaporation temperatures

The suction line is also the point where the designer must be more careful with the relationship between pressure drop and fluid velocity since the refrigerant in a gaseous state has a low density making it difficult to drag oil. Typical speeds for the sizing of the suction line range from 5 to 10 m / s, being that in ascending stretches the speed should never be less than 7.5 m / s.  

In systems where the suction line is very long, there will be situations in which it will be necessary to make a decision between maintaining little pressure drop with low speeds, or increasing the speed (with greater losses) looking for a better drag of the oil. In these situations, the pipe that offers an adequate speed should always be selected, even if the efficiency is punished, since it will always be better to have a slightly less efficient system with a correct return of oil than a system with low pressure drop without lubrication or problems in heat transfer.

Download line

In commercial refrigeration it is often not necessary for the designer to perform a load loss calculation on the discharge line since this line is sized by the manufacturer within the condensing unit assembly. In addition, in these coupled systems the length of the line is not considerable so the loss of pressure or oil drag will not be a problem.

- Publicidad -

However, there are systems with remote capacitor where it is necessary to perform a pressure drop analysis. As a rule, the pipe of these systems should be sized for a pressure loss no greater than 5 psi. Typical download line selection speeds range from 10 to 13 m/s. Special attention should be taken to never select diameters that generate speeds greater than 15 m / s since at this point the line may begin to present excessive vibration and high noise levels.

Liquid line

In contrast to the other lines, the liquid line is a segment of the cooling system that does not (or should not) transport refrigerant in a gaseous state. For this reason, the speed of the fluid is not a primary factor for the proper functioning of the installation since the oil is completely mixed with the liquid coolant.

The function of the liquid line is to supply the expansion valve with a constant flow of sub-cooled refrigerant. To perform this task, it is necessary that during the passage of the fluid in the pipe there is no saturation condition resulting from pressure drops. Refrigerant saturation in the liquid line will result in poor system performance as a sequence of poor expansion valve operation.

Commonly the horizontal stretches of the pipe are not a problem in terms of pressure drop, on the contrary, the ascending segments need special attention. High load losses in ascending segments are inevitable, Table 2 shows the pressure drop per meter of upwelling pipe. To avoid poor system performance, it must be ensured that the sub-cooling in the liquid line is sufficient so that even with pressure loss, the  fluid does not suffer saturation. 

Table 2: Pressure drop per meter of uppipe for different refrigerants

The sub-cooling of each system is variable depending on each application, air-cooled condensers commonly offer a sub-cooling of 3 to 6 °K. If due to a high pressure drop the system needs additional sub-cooling, another auxiliary sub-cooling method must be coupled. Table 3 shows the saturation pressure change for each degree of sub-cooling.

Table 3: Saturation pressure change for each degree of sub-cooling for different refrigerants based on a liquid temperature of 40°C

For example, a 7-meter upwelling liquid pipe using R404A will have a pressure drop of 9.24 psi (see table 2), if the condenser gives a sub-cooling of 3 °K the system withstands 21 psi of pressure drop without generating a saturation condition (see table 3). In this case no additional sub-cooling method will be necessary.

Other factors such as dirty filters, excess service valves or solenoid valves should be avoided so as not to generate an excessive pressure drop, which will bring saturation of the fluid also known as "flash gas".

In terms of coolant velocity, it should only be verified that the liquid line is projected with values below 1.5 m/s to avoid the phenomenon known as water hammer, which can occur after the operation of solenoid valves.

General recommendations  

For the correct functioning of the system, the following factors must be considered in the selection of the pipe.

  • Always use L or K type copper pipe
  • Never select the diameters of the lines based on the connections of the  condenser or evaporator unit
  • If selection tables are used, verify that the conditions of calculation of the same are in accordance with the system that is being projected
  • Always search for the pipeline to have the most direct path possible
  • Avoid the use of unnecessary accessories

*Alonso Amor – application engineering coordinator at Heatcraft Brazil.

KNX LATAM presents the

KNX LATAM presents the "Building Automation Days" in Mexico City and Buenos Aires in October: innovation, technology and networking for the future of buildings

Latin America. The building automation community is preparing to host one of the most relevant meetings in intelligent automation and sustainable construction. KNX LATAM announced that in October it...

Just 2 days away: Barranquilla gets ready for the 24th ExpoAcaire 2025

Just 2 days away: Barranquilla gets ready for the 24th ExpoAcaire 2025

Colombia. From August 13 to 15, the Puerta de Oro Event Center will host the 24th ExpoAcaire and the VI International Congress of Commercial and Industrial Refrigeration, the most important meeting...

Greenheck Expands Rooftop Unit Line with New RT-40 Model

Greenheck Expands Rooftop Unit Line with New RT-40 Model

United States. Greenheck announced the addition of the Model RT-40 to its rooftop unit (RTU) portfolio, expanding HVAC solutions with capacities from 6.5 to 10 tons of packaged DX cooling, 1,200 to...

Systemair offers free webinar on good practices in UMAs

Systemair offers free webinar on good practices in UMAs

Mexico. This August 14, at 10:00 a.m. (CDMX time), Systemair will hold a high-level technical webinar focused on "Good practices in installation and maintenance of Air Handling Units (UMAs)".

High temperatures put Mexico's cold chain in check

High temperatures put Mexico's cold chain in check

Mexico. The current weather season, marked by heavy rains, intermittent heat and floods, is affecting the logistics and operation of companies throughout the country. This scenario represents a...

MultiFRÍO and Dicoma Refrigeración, winners of the CALA Awards HVAC/R 2025

MultiFRÍO and Dicoma Refrigeración, winners of the CALA Awards HVAC/R 2025

Dominican Republic. The 2025 edition of Refriaméricas was the setting for the presentation of the prestigious CALA Awards HVAC/R. This award highlights the most innovative and technically...

Chile boosts sustainable industrial refrigeration with transcritical CO₂ pilot project

Chile boosts sustainable industrial refrigeration with transcritical CO₂ pilot project

Chile. In a decisive step towards cleaner and more efficient refrigeration, Chile will implement a pilot project to introduce transcritical CO₂-based cold-heat pumps in its domestic industry.

LG Electronics brings together the 30 most influential HVAC consultants in Latin America

LG Electronics brings together the 30 most influential HVAC consultants in Latin America

Panama. The 2025 edition of the LATAM Consultant Club highlighted technological advances, regional success stories, and the launch of the new Multi V i R32 system.

Cooling Data Centers: The New Energy Challenge of the Digital Revolution

Cooling Data Centers: The New Energy Challenge of the Digital Revolution

International. The rise of artificial intelligence is putting unprecedented pressure on global data center infrastructure. The growing adoption of models such as ChatGPT, Gemini, and other...

Climatizadora reinforces its commitment to the HVAC-R industry at an important congress in Panama

Climatizadora reinforces its commitment to the HVAC-R industry at an important congress in Panama

Panama. The company participated as an official sponsor of the XVIII International Congress of Electrical, Mechanical and Industrial Engineering, held from July 22 to 24 in Panama City.

Free Subscription
Remember Me
SUBSCRIBE TO OUR NEWSLETTER
DO YOU NEED A SERVICE OR PRODUCT QUOTE?
LASTEST INTERVIEWS
SITE SPONSORS










LASTEST NEWSLETTER
Ultimo Info-Boletin