Electrical installations in air conditioning

Electricidad en HVACWe present a series of recommendations and aspects to take into account to develop a correct electrical installation of an air conditioner.

By Jimy Danelli*

Air conditioning professionals are always receiving installation projects previously calculated to condition certain areas, however, the conditions of each space where the equipment will be installed do not have all the plumbing, electricity and even infrastructure requirements necessary for a correct installation.

The correct installation of an air conditioner consists of several parts, a good location in a suitable infrastructure space, connection of fluid drainage pipes (plumbing) and electrical protection. The latter I want to detail in this article, although it is something very simple.

- Publicidad -

This guide is aimed at complementing the knowledge of anyone who wants to experiment with electricity by assuming the risks that this represents; the one who works in the field and needs a little help to solve and carry out a task of this type.

Air conditioning systems are characterized by relatively high consumption, and depending on their characteristics (hot / cold) can be used seasonally or all year round. For this reason they must be considered as individual elements within the circuit and for their correct electrical protection a particular branch is derived for their power.

This is important because if we make the mistake of plugging the device into any socket we have nearby, we run the following risks:
a) We overload the circuit of outlets, this can translate into triggers of thermal protection when other sockets are used with other devices.
b) We are using a pre-existing circuit that was not calculated for these benefits, therefore, in the best case, only the thermal will jump.
c) By regulation and for convenience, it is necessary to be able to cut the energy individually for maintenance and other necessities. In Figure 1 we show the circuit of a characteristic house.

Circuito de luces

Figure 1.

As can be seen in the graph, there is a circuit for lights, another for sockets (where we connect low consumption devices: chargers, blenders, fans, etc.), and others for devices of higher consumption. Individually each secondary circuit has a thermal protection and wiring according to the current and power performance. As a general cut we have the differential switch (ID) that protects us from discharges dangerous to health. Limiters, fuses and other general cut elements are also used on the main board.

How do I proceed to calculate the protections, cables and costs?
I could elaborate on the theory of calculations and sizing that this work covers, but that is a subject of study of the profession and I am not interested in dealing with it here. I better want to explain the procedure with a simple and real example that I had to perform recently.

- Publicidad -

First we have to recognize the place where it is already structurally installed. It is strictly forbidden to use extension cords and adapters (irregularities that my client had). Identify the make and model of the device, measure the distance to the sectional box, and plan the shortest path of cables from the board to the socket that should be close (1m) to the air. Drawing a sketch we have something like this (figure 2):

Instalaciones eléctricas en aire acondicionado

Figure 2.

Then we have to take phase and neutral of the equipment, ground discharge from a common terminal inside the board. There will be installed a thermomagnetic switch (breker or disconnective) that will govern over the Air. Drill through the wall.

On the other hand, channel (with cable channel in compliance with the client / user) to an octagonal verification box nearby.

From there the three cables will be probed through the tube inside the wall to near the destination, passing through three octagonal boxes and a rectangular one of outlets. From the last to the outside socket should be put near the Air, cable channel (very discreet and neat because it is an aesthetically very pleasant living room, but when installing the air must take into account the aesthetics of said installation).

- Publicidad -

Therefore to start with the calculations we have to look in the user manual (if you had the prudence to save) or in the Surrey site where we find the technical specifications for each model.

The following example of table (1) tells us the physical capabilities and properties:

Instalaciones eléctricas en aire acondicionado

Table 1.


Table 2 shows the consumption:

Instalaciones eléctricas en aire acondicionado

Table 2.

Note that the highlight is the model to protect "cold alone" and "cold heat" to see the case of higher consumption. Giving the current value between 9.13A and 10.08A.

Calculation of the section of cables to be used
For that we consult in the following table (3) which of the commercial values (standard) fits the amperage requirements.

Instalaciones eléctricas en aire acondicionado

Table 3.

As a general rule it is understood that the 1.5 mm2 conductor (13A maximum that supports) would be useful to our purpose. The 2.5mm2 conductor (18A maximum that supports) is recommended. In this case the choice of conductor was limited to conductors of 1.5 for pre-existing structural reasons (the pipe with little space to channel more cables).

It must be considered that the pipe must have free space to avoid overheating. Another good reason is to lower the cost of materials (2.5 more copper, more expensive). It is made clear that whenever possible, using 2.5 is safer.

Calculation of meters of cables to be used
As seen in the sketch, we are about 13m long and to that we must add between climbs, descents and turns, 6m more. How is it better as long as it is over and not missing, that they are 25m of 1.50mm2 cable. Since we must carry three cables, which are of the standardized colors:
25m brown (phase)
25m celestial (neutral)
10m green/yellow
In total 60m of cable.

Thermomagnetic Switch Calculation
Of the commercial values that we have 10AMP or 20 AMP, I stayed with the 16, so that it does not work very to the limit, but, as we will see later, with one of 10 it would go well and the cables would be well protected as well. It can be unipolar or bipolar (Figure 3).

Instalaciones eléctricas en aire acondicionado

Figure 3.

Calculation of outlet
What should be done is to look at the plug of the artifact (20A), from there look for a 20A socket.

Figure 4.

Calculation of materials

Instalaciones eléctricas en aire acondicionado

Table 4.

These prices (in dollars) are approximate and estimated. Rather, they are indicative, every time a budget is put together, the updated prices should be consulted.

Calculation of construction time
This depends a lot on the skill of each one and is necessary especially if it is for a client. It is important to determine the intervals in which a scheduled cut must be made and that there are no downtime due to not being able to cut (for example servers in business). In addition, setting a cap to achieve a goal and gives the client an overview of the work.

Broadly speaking, you must work on the 30' sectional board (uncover, place, connect, drill, channel cables, etc.)
30' more on the other side placing cable channel.
30' passing tape and cable in each section between box and inspection box (x3)
30' more placing cable channel and socket at the end.
In total it gives 2 hours 30' but it is not bad to round in 4 h (half a day of laburo) since unforeseen events may arise (unforeseen events will arise).

Labor cost calculation
This is very particular and there is no set rule. That is, each professional sets their fees depending on experience or personal pretensions.

a) By time: if one intends to earn US$20 per hour, then, apart from the US$85 in materials, the client is given US$80. In this way an unbeatable budget is spent economically speaking, but the stipulated times must be met by doing quality work, otherwise we lose out.

b) By mouths: Some prefer in advance to put a price to each section where you work (mouths) and so if a mouth is a passage box has a price and is a shot and period, another. This is prefixed and detailed for example: in the 50p board, in a 30p pitch box, the 40p Air outlet, the 20p pipes. Leaving about 50 + 30*5boxes + 40 + 20*2channels = 280p

c) By meters of circulation: we can put a price to each meter of work differentiating those that are passed from cable in pre-existing pipe (10p / m) and external channeling (5p / m). Remaining about 130preex + 30channel = 160p

This is for guidance. The details of my billing in this case I reserve, but we must say that after trying the different methods of budgeting, the "b" is the most ideal since it is more realistic.

It is a simple but important job for the proper functioning of the circuit. The current measurement gave 6.7A (which made me think of the thermal of 10A) and the optimal result is when the work is finished, it is not noticeable that there are added cables (the cable channel or gutter behind the board must be the most hidden). Obviously in the sectional board you have to label the new control for user management.

These recommendations allow the professional to have an estimate of the tasks and activities that must be carried out only in the electrical installation to install a Split or compact equipment.

Instalaciones eléctricas en aire acondicionado

Figure 5.

* Jimy Danelli is an air conditioning and refrigeration maintenance consultant. You can write to the email: [email protected]

Duván Chaverra Agudelo
Author: Duván Chaverra Agudelo
Jefe Editorial en Latin Press, Inc,.
Comunicador Social y Periodista con experiencia de más de 16 años en medios de comunicación. Apasionado por la tecnología y por esta industria. [email protected]

11 thoughts on “Electrical installations in air conditioning”

• If you're already registered, please log in first. Your email will not be published.
  1. Andres Franco
    Thursday, 28 March 2024 11:36
    Hola por favor ayudenme con esto sean tan amables.
    ¿Calcular el breake y el cable conductor para un split tipo ducto de 24.000 btu/h con un voltaje de 240 y una potencia de 3.000 vatios?
  2. Jose g Estaba
    Monday, 18 September 2023 06:07
    Buen dia en mi red electrica 220v. El suministro q llega cuando mido tension es de 246v a 250v. Eso podría afectar mi equipo de aire
    acondicionado .220v. Onpuede operar con ewe voltaje q llegua
    1. Duván Chaverra Agudelo dchaverra2020
      Wednesday, 20 September 2023 09:24

      Hola, Jorge. El Ing. Jimy nos compartió la siguiente respuesta a tu pregunta: "Los sistemas normalmente viene diseñados para trabajar un 10% más o menosl es decir que hasta un aproximado de 242v no deberían presentarse problemas, pero al estar por encima de 242 pasando de los 250v puede generar daños, no tanto al motor condensador, evaporador y mucho menos al compresor,  pero sí en algunos componentes como la tarjeta de control, que son componentes electrónicos más delicados y que pueden sufrir recalentamientos como en el puente rectificador, en los transformadores, entre otros elementos electrónicos más propensos a sufrir por los sobre voltajes o por las caídas de tensión que estén por debajo de un 10%".

  3. Albert
    Sunday, 10 September 2023 18:02
    si instalo un térmico adecuado para el split 220v 12000BTU digamos uno de 16A; sería necesario además instalar un protector de voltaje?
    1. Duván Chaverra Agudelo dchaverra2020
      Monday, 11 September 2023 14:16

      Hola, Albert, el Ing. Danelli nos envió la siguiente respuesta a tu consulta: "Perfecto, los protectores térmicos, como su nombre lo indican, protegen únicamente por variación de amperaje y temperatura, si el voltaje falla no lo lee directamente. Esto puede que afecte el equipo si por ejemplo el voltaje está muy por encima, o por el contrario muy bajo, claro que cuando el voltaje baja el amperaje sube y puede que dispare el térmico, pero esto depende del ajuste del protector térmico".

  4. Hola
    Thursday, 29 September 2022 20:32
    Hola buenas noches quería saber si un rígido 14 me aguanta para un toma a 220 para un aire de ventana de según el manual el cableado debería aguantar 16 Amperios
    1. Duván Chaverra Agudelo dchaverra2020
      Monday, 11 September 2023 15:04

       Hola, Paola, el Ing. Jimy compartió la siguiente respuesta a tu consulta: "Es recomendable utilizar un cable N12 para que en posibles arranques que supera 3 veces la corriente nominal no esté en el límite del aislante de ese conductor"..

  5. Carlos Medina
    Friday, 27 May 2022 17:37
    Hola, gracias muy bien explicado, tengo una duda si en una casa quiero colocar 2 split, debo colocar 1 automático para cada uno, o puedo utilizar 1 de 16 Amp para el circuito de A/A. Gracias.
    Pd. más allá de que correspondería uno para cada uno por tema mantenimiento.
    1. Duván Chaverra Agudelo dchaverra2020
      Monday, 11 September 2023 15:05

      Hola Carlos, el Ing. Danelli nos compartió la siguiente respuesta a tu consulta: "Hola saludos amigo Carlos, efectivamente es necesario colocar uno para cada equipo, ya que pudiera generarte una falla y se desconectarían los dos a la vez, otra cosa es que al conectar pueden arrancar simultáneamente superando el RLA para ese automático".

  6. Melvin Valdez zabala
    Thursday, 17 February 2022 15:34
    saludos cómo puedo capacitarme reparación de aire acondicionado
    1. Duván Chaverra Agudelo dchaverra2020
      Monday, 21 February 2022 07:57

      Hola Melvin, lo primero que debes hacer es buscar con tus respresentantes de marca, quienes deben generar espacios para capacitarte. Si eres indipendiente, te recomendamos que te acerques a las asociaciones relacionadas en tu país. Las asociaciones también realizan capacitaciones constantemente.

      Saludos.

Leave your comment

In reply to Some User
Free Subscription
SUBSCRIBE TO OUR NEWSLETTER
DO YOU NEED A SERVICE OR PRODUCT QUOTE?
LASTEST INTERVIEWS

Entrevista a Jaime Maldonado, Presidente de Air-Con Inc

En entrevista con ACR Latinoamérica, Jaime Maldonado, Presidente de Air-Con Inc, destacó los proyectos que tiene la compañía para este año 2024, sobre todo con la transición de los nuevos refrigerantes. Además, Air-Con estará como expositor en Refriaméricas Miami, y Jaime nos habló sobre sus expectativas con el evento y lo que darán a conocer para todos los visitantes.

Webinar: Armstrong y Energía de Distrito

Por: Rafael Behar, Gerente de Apoyo de Aplicación, Armstrong Fluid Technology Los sistemas de energía de distrito se caracterizan por una o más plantas centrales que producen agua caliente, vapor y/o agua fría, que luego fluye a través de una red de tuberías aisladas para proporcionar agua caliente, calefacción y/o aire acondicionado a los edificios cercanos. Los sistemas de energía de distrito sirven a una variedad de mercados de uso final, incluidos los centros de las ciudades (distritos comerciales centrales), campus universitarios, hospitales e instalaciones de atención médica, aeropuertos, bases militares y complejos industriales. Al combinar cargas para múltiples edificios, los sistemas de energía urbana crean economías de escala que ayudan a reducir los costos de energía y permiten el uso de tecnologías de alta eficiencia. En este seminario web vamos a introducir a Armstrong Fluid Tecnología y su dirección para la energía urbana con enfoques en plantas de calefacción. https://www.acrlatinoamerica.com/20...

Webinar: Mejores Practicas para la Optimización de Sistemas

Importancia de la correcta automatización de plantas de agua helada con el objetivo de pasar al siguiente nivel, que es la optimización de los sistemas para obtener una mayor eficiencia energética y ahorro del costo operativo y de mantenimiento. Por: Camilo Olvera Rodríguez, Gerente de Ventas - México, ARMSTRONG FLUID TECHNOLOGY https://www.acrlatinoamerica.com/20...

Webinar: Enfriando el futuro: Las nuevas tendencias en refrigerantes para supermercados y almacenes

https://www.acrlatinoamerica.com/20... Únete a nosotros en este emocionante Webinar sobre las últimas tendencias en refrigerantes para supermercados y almacenes. Descubre cómo mantener tus productos frescos de manera eficiente, mientras contribuyes a la sostenibilidad y cuidado del medio ambiente. En esta sesión, exploraremos las innovaciones más recientes en refrigerantes ambientalmente preferibles, incluyendo tecnologías avanzadas de enfriamiento. Aprenderás sobre las ventajas de adoptar estas nuevas soluciones, no solo en términos de eficiencia energética, sino también en la reducción de emisiones y el cumplimiento de regulaciones ambientales. Por: Guillermo Brandenstein, Sr Account Manager - Honeywell

Webinar: ¿Es adecuada la forma de vender en las empresas HVAC/R?

En esta presentación se tratarán puntos neurálgicos sobre cómo lograr vender sin necesidad de licitar, teniendo muy presente que el cliente no nos compre porque somos los más baratos sino porque somos su mejor opción. Por: Ing. Rolando Torrado, CEO - Rolando Torrado https://www.acrlatinoamerica.com/20...
Load more...
SITE SPONSORS










LASTEST NEWSLETTER
Ultimo Info-Boletin