Good practices in compressors

Working within the range of operations in compressors can make a difference in terms of a long service life and correct operation of the same, not doing so, can have serious consequences.

By: Santiago Jaramillo H.

During the sixth version of Refricolombia, held last July in the city of Bogotá, one of the academic talks with the greatest impact on the audience was the one guided by the engineer Fernando Becerra Ariza, sales manager of the Danfoss company in Colombia and Ecuador, and which was called "Consequences of working outside the range of operation in compressors". Given this positive acceptance, the magazine ACR LATINOAMÉRICA will share in this edition with all its readers a complete report of what this was, thanks to the special collaboration of the speaker.

To start the compendium of the talk, our guest warns about what are the main problems that can affect a compressor when working outside the range. It also ensures that working within the range of pressures and temperatures in a compressor is the guarantee to ensure optimal operation and long service life.

According to Becerra, the main damages that occur in these equipment are "the high pressures in suction forcing the electric motor to high loads out of design, causing its breakdown. The low suction pressure, in some cases exceeds the compression ratios of the coolant causing high discharge temperatures, also causing oil burning and creation of acids that attack the varnish of the engine and end with its electric burning. In the case of scroll type compressors the operating range of some models must be respected to operate only in high as indicated by its manufacturer. Another damage is high discharge pressures, caused by poor condensation or high refrigerant charge, causing an increase in energy consumption. Likewise, the low discharge pressures, product of low ambient temperatures, incur in pressure drop in the expansion valve decreasing, in passing, its filling capacity".

Return of liquids

- Publicidad -

Already moving on to specific issues such as the causes of the return of liquids and their possible solutions, the representative of the company Danfoss indicated that "first of all it must be verified that there is indeed a return of liquid to the compressor, the total overheating of the system must be measured (evaporation temperature - temperature 30 centimeters before the compressor) if its value is zero the refrigerant reaches the compressor liquid (verify it with the oil viewer). of the same, which will present foam)".

As far as determining the reasons for a liquid return is concerned, our expert recommends following, in your order, the following discard procedures:

  • Verify that the evaporator is not blocked from ice.
  • Check that the evaporator fans are operating.
  • Discard high refrigerant charge, confirm that the high pressure is correct according to the type of condenser and ambient temperature. In this case the viewfinder will be 100% liquid filled.
  • Check if the expansion valve is large, this will be determined according to the operating conditions and thermal load.
  • Check the low thermal load in the system, if it has all its elements sized for a given thermal load and is subjected to one of 20 or 30% below its design, the thermostatic valve will not maintain an overheating in the evaporator generating liquid return, not being so if electronic expansion valve is used.

If all of the above is correct, the conclusion is that the evaporator is undersized. Before completing the refrigerant charge, the system will return liquid to the compressor.


Overheating in compressors

As Becerra acknowledges, "the consequences of high overheating are high discharge temperatures and an increase in the energy consumption of the system. If the coolant overheats, the cooling of the compressor's electric motor is deficient, causing it to be triggered by thermal repeatedly. Likewise, the discharge increases its temperature, if we are close to the maximum compression ratio of the refrigerant, it will exceed 120° C in the discharge causing the burning and formation of acidity in the oil. "

Meanwhile, and as our guest warns, "the increase in energy consumption is due to the decrease in the density of the refrigerant when it is overheated, as a consequence the displaced mass is lower and the compressor must operate longer to meet the temperature of the system".

As for the characteristics that must be given for a good compression ratio, the sales manager of Danfoss assures that "respecting the limits of each refrigerant to avoid high discharge temperatures, being critical the R22, and not exceeding the compression ratio of the compressor design, usually they are usually in 12: 1", would be good practices.

- Publicidad -

On the other hand, Becerra said that to maintain the operating range of the compressor according to the refrigerant used "the main thing is to preserve its initial design, but it is very important that maintenance guarantees it. In addition, the pressures must be maintained in their compressor operating range and, in turn, the total controlled overheating inside the evaporator at 5°C and outside the evaporator as small as possible, so that the total SH is less than 20°C."

Lubrication problems

Another topic highlighted by Becerra Ariza during his conference at Refricolombia 2009 were the factors that can cause lubrication problems and a decrease in the useful life of the compressor, so our guest presented the following problems.

  • Very high or low level of lubrication, maintaining the level at 1/2-3/4 of the visor and ensuring cleanliness and quality of the oil are key.
  • Poor pipe design or poor design of rack level control systems cause a lack or excess of oil in the compressor.
  • Lack of oil: product of no return due to suction diameters or large discharges, high overheating, large return traps, etc.
  • Excess oil: due to high oil load, sudden oil returns in systems that accumulate it in evaporators or pipes, or poor installation of the level control system in racks, etc.

As a consequence of the above factors there will be a decrease in the life of the compressor or immediate damage.

Poor cleanliness and moisture in the system

When asked about the consequences of poor cleaning of the compressor, Becerra stressed that the most frequent are "the cuprous oxide produced at the time of welding without nitrogen flow, plus all the cutting and dirty particles that go to the shell of the compressor scratching and braking its moving parts, so it is necessary that a suction filter is always installed to eliminate this problem that is very frequent in our environment".

In the case of the recommendations to avoid moisture in the system, the Danfoss representative indicated that the key is in the "initial cleaning of exchangers and pipes, use of filter dryers and not exposing the oils and system to the environment for more than five minutes."

Author: J. ALEJANDRA GARCIA

No thoughts on “Good practices in compressors”

• If you're already registered, please log in first. Your email will not be published.

Leave your comment

In reply to Some User
Free Subscription
SUBSCRIBE TO OUR NEWSLETTER
DO YOU NEED A SERVICE OR PRODUCT QUOTE?
LASTEST INTERVIEWS

Entrevista a Jaime Maldonado, Presidente de Air-Con Inc

En entrevista con ACR Latinoamérica, Jaime Maldonado, Presidente de Air-Con Inc, destacó los proyectos que tiene la compañía para este año 2024, sobre todo con la transición de los nuevos refrigerantes. Además, Air-Con estará como expositor en Refriaméricas Miami, y Jaime nos habló sobre sus expectativas con el evento y lo que darán a conocer para todos los visitantes.

Webinar: Armstrong y Energía de Distrito

Por: Rafael Behar, Gerente de Apoyo de Aplicación, Armstrong Fluid Technology Los sistemas de energía de distrito se caracterizan por una o más plantas centrales que producen agua caliente, vapor y/o agua fría, que luego fluye a través de una red de tuberías aisladas para proporcionar agua caliente, calefacción y/o aire acondicionado a los edificios cercanos. Los sistemas de energía de distrito sirven a una variedad de mercados de uso final, incluidos los centros de las ciudades (distritos comerciales centrales), campus universitarios, hospitales e instalaciones de atención médica, aeropuertos, bases militares y complejos industriales. Al combinar cargas para múltiples edificios, los sistemas de energía urbana crean economías de escala que ayudan a reducir los costos de energía y permiten el uso de tecnologías de alta eficiencia. En este seminario web vamos a introducir a Armstrong Fluid Tecnología y su dirección para la energía urbana con enfoques en plantas de calefacción. https://www.acrlatinoamerica.com/20...

Webinar: Mejores Practicas para la Optimización de Sistemas

Importancia de la correcta automatización de plantas de agua helada con el objetivo de pasar al siguiente nivel, que es la optimización de los sistemas para obtener una mayor eficiencia energética y ahorro del costo operativo y de mantenimiento. Por: Camilo Olvera Rodríguez, Gerente de Ventas - México, ARMSTRONG FLUID TECHNOLOGY https://www.acrlatinoamerica.com/20...

Webinar: Enfriando el futuro: Las nuevas tendencias en refrigerantes para supermercados y almacenes

https://www.acrlatinoamerica.com/20... Únete a nosotros en este emocionante Webinar sobre las últimas tendencias en refrigerantes para supermercados y almacenes. Descubre cómo mantener tus productos frescos de manera eficiente, mientras contribuyes a la sostenibilidad y cuidado del medio ambiente. En esta sesión, exploraremos las innovaciones más recientes en refrigerantes ambientalmente preferibles, incluyendo tecnologías avanzadas de enfriamiento. Aprenderás sobre las ventajas de adoptar estas nuevas soluciones, no solo en términos de eficiencia energética, sino también en la reducción de emisiones y el cumplimiento de regulaciones ambientales. Por: Guillermo Brandenstein, Sr Account Manager - Honeywell

Webinar: ¿Es adecuada la forma de vender en las empresas HVAC/R?

En esta presentación se tratarán puntos neurálgicos sobre cómo lograr vender sin necesidad de licitar, teniendo muy presente que el cliente no nos compre porque somos los más baratos sino porque somos su mejor opción. Por: Ing. Rolando Torrado, CEO - Rolando Torrado https://www.acrlatinoamerica.com/20...
Load more...
SITE SPONSORS










LASTEST NEWSLETTER
Ultimo Info-Boletin